DIGSI 5 permits all functions to be configured and com-bined as required.
Up to 40 analog channels
Fast-Scan Recorder
Up to 2 slow-scan recorders
Up to 5 continuous recorders and 2 trend recorders
Power quality recordings according to IEC 61000-4-30 (harmonics, THD, TDD - in preparation)
Sequence-of-events recorder for continuous recording of binary status changes and IEC 61850 GOOSE messages
Usable as Phasor Measurement Unit (PMU) according to IEEE C37.118 protocol
Transmission of the records and triggering via IEC 61850 GOOSE messages
Variable sampling frequencies parameterizable between 1 kHz and 16 kHz
Distribution of the mass storage of 16 GB to the various recorders by the user as desired
Intelligent monitoring routines of the storage medium ensure a high level of availability and completeness for the archived data
Lossless data compression
Time synchronization via Precision Time Protocol (PTP) IEEE 1588 protocol, IRIG-B, DCF77, and SNTP
Routing of the measured values to the individual recorders as desired
Combination of the measuring groups for the power calculation as desired
Quality attributes for representing the instantaneous signal quality in the time signal view
Trigger functions of a function block are fundamental component value, RMS value, zero-sequence, positive-sequence, negative-sequence system power, frequency power, Σ active power and Σ reactive power
Level trigger and gradient trigger for every trigger function
Flexible cross trigger and system trigger, manual trigger
Creation of independent trigger functions with the graphic automation editor CFC (continuous function Chart)
Trigger functions via a combination of single-point, doublepoint indications, analog values, binary signals, Boolean signals and GOOSE messages
Consistent monitoring concept
Auxiliary functions for easy tests and commissioning
Special test mode for commissioning
Integrated electrical Ethernet RJ45 for DIGSI 5 and IEC 61850 (reporting and GOOSE)
Redundancy protocols PRP and HSR
Cyber security to NERC CIP and BDWE Whitepaper requirements
Up to 4 pluggable communication modules usable for
different and redundant protocols
Intelligent terminal technology enables prewiring and a simple device replacement