Gas-insulated switchgear NXPLUS C WIND

Maintenance-free for lifetime

Description

NXPLUS C WIND
NXPLUS C WIND

  • Up to 36 kV, up to 25 kA, 1000 A busbar, 630 A
    and 1000 A feeder

  • Metal-enclosed

  • Single-busbar

  • Gas-insulated

  • Hermetically enclosed

  • Factory-assembled, type-tested switchgear
    according IEC 62 271-200

  • Customer's Benefit:
    - Environmental Independence
    - Compactness
    - Maintenance-free Design
    - Personal Safety
    - Security of Operation, Reliability
    - Cost-efficient, Ecological


Technical Data

Rated voltage

kV

36

Rated frequency

Hz

50/60

Rated short-duration power-frequency withstand voltage

kV

70

Rated lightning impulse withstand voltage

kV

170

Rated peak withstand current

kA

63

Rated short-circuit making current

kA

63

Rated short-time withstand current, 1 s

kA

25

Rated short-circuit breaking current

kA

25

Rated normal current of busbar

A

1000

Rated normal current of feeder

A

630 and 1000*

Degree of protection - Primary part
Degree of protection - Secondary part

IP65
IP3XD

Dimensions
- Width (Circuit-breaker panel)
- Width (Disconnector panel)
- Depth with rear duct
- Height of the panels


mm
mm
mm
 mm


600
450
1000
1900

* Circuit breaker panel with a rated current of 630 A and
   disconnector panel with a rated current of 630 A and 1000 A

Design and construction

Partition Class:

PM (metallic partition)

Loss of service continuity category panels:

LSC 2

Accessibility of Compartments (enclosure):
- Busbar compartment:
- Switching device compartment:
- Low-voltage compartment:
- Cable compartment:

 
tool-based
non accessible
tool-based
tool-based

Internal arc classification

Designation of internal arc classification IAC for
- Wall-standing arrangement
- Free-standing arrangement

 
IAC A FL 25 kA, 1 s
IAC A FLR 25 kA, 1 s

Type of accessibility A
 
 
 
- F
- L
- R

Switchgear in closed electrical
service location, access "for
authorized personnel only"
(according to IEC 62271-200)
Front
Lateral
Rear
(for free-standing arrangement)

Arc test current

25 kA

Test duration

1 s


Front and side view

NXPLUS C Wind Circuit-breaker panel Type LS 630 A

 

Please see further details in catalogue (Catalogue can be found under Download).

References

Selective References

Customer

Country

Dong Energy

Denmark

ERG Renewables

Italy

EDP Renovaveis

Spain

EnBW AG

Germany

Arge EGS PPS

Germany

Vestas

India

E.ON Climate and Renewables

Denmark, UK

Dalekovod d. d.

Croatia

res Renewable Energy Systems Ltd.

UK

Enel Green Power S.p.A.

Romania

juwi Wind GmbH

Germany

Community Windpower Ltd.

UK

Nordex Energy GmbH

Germany

Centrica Lincs

UK

Karara Mining Ltd.

Australia

Scottish & Southern Energy

UK

Sepisa S.A. de C.V.

Mexico

EWE Netz GmbH

Germany

RWE AG

Germany

EDF Energy Renewables

Denmark

Statkraft AS

Sweden

Grupo Coyre

Mexico

ICA

Mexico

REpower AG

Germany

HSE AG

Germany

WindMV GmbH

Germany

Villeroy & Boch AG

Germany